PCC (Power Control Center)

PCC (Power Control Center)

Main power distribution with high fault withstand, selective protection, energy metering & communication for plant-wide reliability.
System
415 V, 50 Hz, 3Ø, 4W
Busbar
Up to 6300 A Cu/Al, 50–100 kA 1s
Ingress
IP54/IP55 (in), IP65 kiosk (out)
Form
Form 2b/3b/4b
Temp Rise
Verified per type design
Contact

High-End Technical Details

  • Construction: Modular bolted CRCA 2.0 mm; CNC punched; 7/9-tank pre-treatment + 70–80μ powder coat.
  • Busbar System: ETP Cu/Al tin-plated, sleeves; shrouded supports; Belleville washers at joints.
  • Incomers & Couplers: Draw-out ACBs with LSIG/E/F; ZSI capable; mech+elec interlocks.
  • Cable Management: Top/bottom entry, 300–600 mm alleys, tie rails, earthing/glanding kits.
  • Arc-Mitigation: Relief vents/ducts, pressure flaps, arc-resistant options (req).
  • Digitalization: 0.2S/0.5S MFMs, Ethernet gateways, Modbus RTU/TCP, cloud logger.

Protection & Metering

  • ACB LSIG
  • U/O Voltage & Phase failure
  • SPD Type 2
  • Earth fault
  • Busbar temp sensors (opt)

Standards / Type-Tests

  • IEC 61439-1/2
  • IEC 60529
  • ASTA/CPRI design verifications

Options / IO / Integrations

  • DG/UPS sync, split bus
  • HMI 7”/10”, PQ meters
  • Space heaters & humidity control
  • Custom RAL/SS enclosures
11 kV VCB Switchgear

11 kV VCB Switchgear

Indoor metal-clad withdrawable VCB; numerical relays; feeder/incomer/bus-coupler configs.
Voltage
12 kV (Um 12)
Current
630–2000 A
Icw
25/31.5 kA 3s
BIL
75 kVp
Ingress
IP4X/IP2X
Contact

High-End Technical Details

  • Compartmentalization: LSC2B-PM; segregated bus/cable/CB; earthed shutters.
  • Breaker Truck: Rack in/out/test; mechanical keys & padlock.
  • Relays & CT/PT: 50/51/50N/51N/67 etc.; supervised trip circuits.
  • Testing/Routine: Dielectric, primary injection, scheme validation.

Protection & Functions

  • OC/EF
  • Directional OC/EF (opt)
  • U/O voltage & freq
  • Busbar differential (opt)

Standards / Type-Tests

  • IEC 62271-200
  • IEC 60071
  • IS 3427

Options / SCADA / IO

  • IEC-104/61850 SCADA
  • Arc sensors
  • Space heaters